BURNER FLAME ADJUSTMENT For
Dearborn Model DRC Vent-Free Heaters

Your
heater has been factory tested and adjusted. Due to variations in heating values
and gas pressures, it may be necessary to make an adjustment to the burner air
shutter setting. Figure 1 shows the correct flame characteristics and required
adjustments. A small hard blue flame or a flame blowing off the burner ports or
lighting back at the burner orifice indicates too much primary air and the air
shutter should be closed. A soft, blurred or yellow tipped flame indicates lack
of primary air and the air shutter should be opened.
|
- Light the burner.
- After the burner has been in
operation for 3 minutes or more, observe the burner flame, Figure 1, and make
the air shutter adjustment, if needed.
- Visually check the burner flame
periodically. See Figure 1. Any change in the burner flame from that obtained in
Step 2 above may indicate a dirty burner or burner compartment. Turn the gas off
at the line cut-off valve, open the burner access door and allow the heater to
completely cool. Clean the burner area with a vacuum cleaner attachment.
- Once each year, the burner may
need cleaning. This can be done with a vacuum cleaner attachment or bottle
brush. Clean burner area, burner air intake, air shutter and burner ports with a
brush or blow them out with a vacuum cleaner or tire pump. See Figure 1.
- We strongly recommend having a
qualified service agency inspect the unit for proper operation before the start
of each heating season.
- The orifice spud supplied for
the burner has been drilled to specified gas characteristics to provide proper
operation and the required gas input at the manifold pressure shown on the name
plate.
|
A. Not
Enough Heat
- Cause: Space to be
heated too large.
Remedy: Install an additional or larger heater.
- Cause: Insufficient gas
input
Remedy: Check with dealer. Orifice may be undersized.
- Cause: Loss of heated
air to outside through fireplace.
Remedy: Install damper in fireplace.
- Cause: Loss of heated
air to outside through ventilator fan.
Remedy: Reduce air flow through
ventilator fan. Install damper.
B. Excessive Heat
- Cause: Space to be
heated too small.
Remedy: Install smaller heater.
- Cause: Excessive gas
input
Remedy: Orifice may be oversized.
C. Main Burner Flame Lazy and Yellow (Also
cause of combustion odors)
- Cause: Gas input too
high or not corrected for high altitude.
Remedy: Check for proper
orifice size.
- Cause: Dust, lint or
dirt in or around burner and air shutter.
Remedy: See
cleaning instructions.
- Cause: Air shutter not
properly adjusted.
Remedy: See adjustment
instructions.
|
D. Delayed
Ignition of Main Burner
- Cause: Pilot burner not
in proper alignment with burner.
Remedy: Check for proper factory
dimensions.
- Cause: Pilot flame too
small.
Remedy: Check for dirty pilot. Check for proper gas pressures.
- Cause: Unit not level.
Remedy:
Re-level unit.
- Cause: Burner ports
clogged.
Remedy: Clean burner.
- Cause: Low gas input.
Remedy:
Clean, incorrect or clogged orifice.
E. Pilot Outage
- Cause: Blockage or
restriction of pilot orifice.
Remedy: See Pilot
Flame Observation.
- Cause: Draft/Air
currents.
Remedy: Locate and correct source of draft/air currents.
- Cause: Oxygen depletion.
Remedy:
Provide fresh air make up to heater area.
F. Flash Back Burning/Main Orifice
- Cause: Improper
combustion air.
Remedy: See adjustment
instructions.
- Cause: Defective burner.
Remedy:
Replace burner.
- Cause: Unit not level.
Remedy:
Level unit.
|